Abstract
In order to handle the situation of power system grounding fault better, this paper built the mathematical model of power system resonance grounding fault based on the resonance grounding principle. And simulated the resonance processes by using MATLAB/SIMULINK/ SIMPOWERSYSTEM (SPS) software. The obtained results show that there will appear zero sequence current at each point of power system when the grounding faults occurrs. And if the circuit has the point of biggest amplitude of zero sequence current, then it is just the fault phases. The simulation data further verified that arc suppression coil grounding could directly decreases the grounding current when the single-phase grounding fault occurred. Moreover, it effectively eliminates the arc from the process and becomes the more reasonable grounding mode
چکیده
بمنظور کنترل وضعیت بهتر خطای اتصال بزمین سیستم قدرت، این مقاله مدل ریاضی خطای اتصال بزمین رزونانس سیستم قدرت مبتنی بر اصل اتصال بزمین رزونانس را ساخت. و فرآیندهای رزونانس را با استفاده از نرم افزار Matlab/Simulink/SimPowerSystem (SPS) شبیه سازی کرد. نتایج بدست آمده نشان میدهند که در آنجا جریان توالی صفر در هر نقطه سیستم قدرت هنگامی که خطاهای اتصال بزمین رخ میدهند، پدیدار خواهند شد. و اگر مدار نقطه دامنه بزرگترین جریان توالی صفر را داشته باشد، سپس آن فقط فازهای خطا میباشد. داده های شبیه سازی همچنین تایید کردند که اتصال بزمین سیم پیچی حذف قوس الکتریکی میتواند مستقیما جریان اتصال بزمین را کاهش دهد هنگامی که خطای اتصال بزمین تکفاز رخ دهد. بعلاوه، بطور موثری قوس الکتریکی را از فرآیند حذف میکند و حالت اتصال بزمین مناسب تری میشود.